1000 kW gas generator set

Jenbacher 1000 kW Natural Gas Gas-Engine Generator
Electrical output 1063 kW
100% | 75% | 50% | |||
|---|---|---|---|---|---|
Energy input | [2] | kW | 2,622 | 2,015 | 1,421 |
Gas volume | *) | Nm³/h | 477 | 366 | 258 |
Mechanical output | [1] | kW | 1,095 | 821 | 548 |
Electrical output | [4] | kW el. | 1,063 | 796 | 529 |
Heat to be dissipated (calculated with 37% glycol) | [5] | ||||
~ Intercooler 1st stage (engine jacket water cooling circuit) | [9] | kW | 187 | 84 | 19 |
~ Intercooler 2nd stage (low-temperature circuit) | kW | 81 | 54 | 32 | |
~ Lube oil (engine jacket water cooling circuit) | kW | 126 | 99 | 86 | |
~ Jacket water | kW | 345 | 310 | 263 | |
~ Surface heat | [7] | kW | 90 | ~ | ~ |
Specific fuel consumption of the genset | [2] | kWh/kWel. h | 2.47 | 2.53 | 2.69 |
Specific fuel consumption of the engine | [2] | kWh/kWh | 2.40 | 2.45 | 2.59 |
Lube oil consumption | [3] | kg/h | 0.33 | ~ | ~ |
Electrical efficiency | 40.6% | 39.5% | 37.2% | ||
Fuel gas LHV | kWh/Nm³ | 5.5 |
*) approximate value for pipeline sizing
[_] Explanations: see 0.10 – Technical parameters
All heat data are based on standard conditions according to Annex 0.10. Deviations from standard conditions may change the values in the heat balance and must be taken into account in the layout of the cooling circuit/equipment (intercooler, emergency cooling, etc.). In the specifications, in addition to the general tolerance of ±8% on thermal output, an additional reserve of +5% is recommended for determining the cooling requirements.
Main dimensions and weights (genset)
Length | mm | ~ 5,700 |
|---|---|---|
Width | mm | ~ 1,700 |
Height | mm | ~ 2,300 |
Weight, empty | kg | ~ 13,600 |
Weight, filled | kg | ~ 14,100 |
Connections | ||
Jacket water inlet and outlet | DN/PN | 80/10 |
Exhaust gas outlet | DN/PN | 250/10 |
Fuel gas (at genset) | DN/PN | 80/16 |
Drain ISO 228 | G | ½'' |
Condensate drain | mm | ~ |
Safety valve – jacket water ISO 228 | DN/PN | 1½''/2.5 |
Lube oil replenishing (pipe) | mm | 28 |
Lube oil drain (pipe) | mm | 28 |
Jacket water – filling (flexible pipe) | mm | 13 |
Intercooler water – inlet/outlet, 1st stage | DN/PN | 80/10 |
Intercooler water – inlet/outlet, 2nd stage [M/N] | DN/PN | 65/10 |
Output / fuel consumption
ISO standard fuel stop power ICFN | kW | 1,095 |
|---|---|---|
Mean effective pressure at standard power and nominal speed | bar | 18.00 |
Fuel gas type | Biogas | |
Based on methane number | Min. methane number | MZ | 135 | 117 d) |
Compression ratio | Epsilon | 12.5 |
Min./max. fuel gas pressure at inlet to gas train | mbar | 80 - 200 c) |
Max. rate of gas pressure fluctuation | mbar/sec | 10 |
Maximum intercooler 2nd stage inlet water temperature | °C | 50 |
Specific fuel consumption of the engine | kWh/kWh | 2.40 |
Specific lube oil consumption | g/kWh | 0.30 |
Max. oil temperature | °C | 90 |
Jacket water temperature, max. | °C | 95 |
Lube oil capacity (filling) | lit | ~ 342 |
c) Lower gas pressure upon request | ||
d) based on methane number calculation software AVL 3.2 |
Engine technical data
Manufacturer | JENBACHER | |
|---|---|---|
Engine type | J 320 GS-D25 | |
Working principle | 4-Stroke | |
Configuration | V 70° | |
Number of cylinders | 20 | |
Bore | mm | 135 |
Stroke | mm | 170 |
Piston displacement | lit | 48.67 |
Nominal speed | rpm | 1,500 |
Mean piston speed | m/s | 8.50 |
Length | mm | 3,320 |
Width | mm | 1,358 |
Height | mm | 2,065 |
Weight, dry | kg | 5,200 |
Weight, filled | kg | 5,700 |
Moment of inertia | kgm² | 8.61 |
Direction of rotation (viewed from flywheel) | left | |
Radio interference level according to VDE 0875 | N | |
Starter motor output | kW | 7 |
Starter motor voltage | V | 24 |
Thermal energy balance
Energy input | kW | 2,622 |
|---|---|---|
Intercooler | kW | 268 |
Lube oil | kW | 126 |
Jacket water | kW | 345 |
Exhaust gas cooled to 180 °C | kW | 506 |
Exhaust gas cooled to 100 °C | kW | 642 |
Surface heat | kW | 48 |
Exhaust gas data
Exhaust gas temperature at full load [8] | °C | 465 |
|---|---|---|
Exhaust gas temperature at bmep = 13.5 [bar] | °C | ~ 494 |
Exhaust gas temperature at bmep = 9 [bar] | °C | ~ 512 |
Exhaust gas mass flow rate, wet | kg/h | 5,657 |
Exhaust gas mass flow rate, dry | kg/h | 5,250 |
Exhaust gas volume, wet | Nm³/h | 4,420 |
Exhaust gas volume, dry | Nm³/h | 3,913 |
Max. admissible exhaust back pressure after engine | mbar | 60 |
Combustion air data
Combustion air mass flow rate | kg/h | 5,208 |
|---|---|---|
Combustion air volume | Nm³/h | 4,030 |
Max. admissible pressure drop across the air intake filter | mbar | 10 |
Basis for exhaust gas data: natural gas: 100% CH4; biogas: 65% CH4, 35% CO2 |
Sound pressure level
Genset a) | dB(A) re 20µPa | 96 |
|---|---|---|
31.5 | dB | |
63 | dB | |
125 | dB | |
250 | dB | |
500 | dB | |
1000 | dB | |
2000 | dB | |
4000 | dB | |
8000 | dB | |
Exhaust gas b) | dB(A) re 20µPa | 122 |
31.5 | dB | |
63 | dB | |
125 | dB | |
250 | dB | |
500 | dB | |
1000 | dB | |
2000 | dB | |
4000 | dB | |
8000 | dB |
Sound power level
Genset | dB(A) re 1pW | 117 |
|---|---|---|
Measurement surface | m² | 120 |
Exhaust gas | dB(A) re 1pW | 130 |
Measurement surface | m² | 6.28 |
a) average sound pressure level on the measurement surface at a distance of 1 m (converted to free-field conditions) according to DIN 45635, precision class 3. | ||
b) average sound pressure level on the measurement surface at a distance of 1 m according to DIN 45635, precision class 2. | ||
The spectra are valid for gensets up to bmep = 18 bar (for higher bmep, add a safety margin of 1 dB to all values per 1 bar of pressure increase). | ||
Engine tolerance ± 3 dB |
Generator technical data
Manufacturer | Leroy-Somer e) | |
|---|---|---|
Type | LSA 50.2 VL10 e) | |
Type rating | kVA | 1,317 |
Driving power | kW | 1,095 |
Ratings at p.f. = 1.0 | kW | 1,063 |
Ratings at p.f. = 0.8 | kW | 1,053 |
Rated output at p.f. = 0.8 | kVA | 1,316 |
Rated reactive power at p.f. = 0.8 | kVar | 790 |
Rated current at p.f. = 0.8 | A | 1,900 |
Frequency | Hz | 50 |
Voltage | V | 400 |
Speed | rpm | 1,500 |
Permissible overspeed | rpm | 1,800 |
Power factor (lagging – leading) (UN) | 0.8 - 1.0 | |
Efficiency at p.f. = 1.0 | 97.1% | |
Efficiency at p.f. = 0.8 | 96.2% | |
Moment of inertia | kgm² | 26.33 |
Mass | kg | 3,300 |
Radio interference level according to EN 55011, class A (EN 61000-6-4) | N | |
Cable outlet | left | |
Ik'' Initial symmetrical short-circuit current | kA | 17.24 |
Ip Peak current | kA | 43.88 |
Insulation class | H | |
Temperature (rise at driving power) | F | |
Maximum ambient temperature | °C | 40 |
Reactances and time constants (saturated) at rated output | ||
xd direct-axis synchronous reactance | p.u. | 2.428 |
xd' direct-axis transient reactance | p.u. | 0.180 |
xd'' direct-axis subtransient reactance | p.u. | 0.109 |
x2 negative-sequence reactance | p.u. | 0.095 |
Td'' subtransient reactance time constant | ms | 20 |
Ta DC time constant | ms | 30 |
Tdo' open-circuit field time constant | s | 4.06 |
e) JENBACHER reserves the right to change the generator supplier and generator type. The contractual data of the manufacturer may change slightly as a result. The contractual electrical output will not change. |
Cooling water circuit
Lube oil heat (engine jacket water cooling circuit)
Nominal output | kW | 126 |
|---|---|---|
Max. oil temperature | °C | 90 |
Nominal jacket water pressure loss | bar | 0.20 |
Safety valve – max. pressure setting | bar | 2.50 |
Jacket water heat (engine jacket water cooling circuit)
Nominal output | kW | 345 |
|---|---|---|
Max. jacket water temperature (engine outlet) | °C | 90 |
Jacket water flow rate | m³/h | 31.7 |
Safety valve – max. pressure setting | bar | 2.50 |
Mixture intercooler (1st stage) (engine jacket water cooling circuit)
Nominal output | kW | 187 |
|---|---|---|
Max. cooling water inlet temperature (intercooler) | °C | 73.8 |
Nominal cooling water pressure / (max. operating pressure) | PN | 10 |
Nominal jacket water pressure loss | bar | 0.40 |
Safety valve – max. pressure setting | bar | 2.50 |
Mixture intercooler (2nd stage) (low-temperature circuit)
Nominal output | kW | 81 |
|---|---|---|
Max. cooling water inlet temperature (intercooler) | °C | 50 |
Intercooler water flow rate | m³/h | 25.0 |
Nominal cooling water pressure / (max. operating pressure) | PN | 10 |
Intercooler water pressure drop | bar | 0.20 |
Safety valve – max. pressure setting | bar | 2.50 |
The final pressure drop will be provided after final order clarification and must be taken from the order documentation (P&ID). |
Technical parameters
All data in the technical specification are based on full engine load (unless stated otherwise) at the specified temperatures and methane number, and are subject to technical development and modification.
All pressure values must be measured and read with gauge pressure gauges (psi.g.).
[1] At nominal speed and standard ICFN conditions according to ISO 3046-1
Efficiency values are based on a new unit (immediately after commissioning). The effects of deterioration during normal operation can be mitigated through regular service and maintenance work. Reference value --> 65% CH4 / 35% CO2
[3] Average value between oil change intervals according to the maintenance schedule, excluding the oil change quantity
[4] At p.f. = 1.0 according to VDE 0530 REM / IEC 34.1 with relative tolerances, all direct-driven pumps included
[7] As an indicative value at p.f. 0.8, valid only for (engine, generator, TCM). Other peripheral equipment is not considered.
* Standard conditions – if the turbocharger design is rated for an intake air temperature > 30°C without derating, the 1st stage intercooler heat must be increased by 2%/°C starting from 25°C. Deviations between 25 and 30°C are covered by the standard tolerance.
* Hot Country application (V1xx) – if the turbocharger design is rated for an intake air temperature > 40°C without derating, the 1st stage intercooler heat must be increased by 2%/°C starting from 35°C. Deviations between 35 and 40°C are covered by the standard tolerance.
The ignition system of the gas engines complies with the radio interference levels of CISPR 12 and EN 55011 class B (30-75 MHz, 75-400 MHz, 400-1000 MHz) and (30-230 MHz, 230-1000 MHz), respectively.
Net brake power that the engine manufacturer declares the engine is capable of delivering continuously at the stated speed between the normal maintenance intervals and overhauls required by the manufacturer. Power determined under the operating conditions of the manufacturer's test bench and adjusted to standard reference conditions.
Barometric pressure: 1000 mbar (14.5 psi) or 100 m (328 ft) above sea level. Air temperature: 25°C (77°F) or 298 K